Motorized
-
3300R:Motorized
Actuators
3300R -
3400R:Motorized
Actuators
3400R
Here is a line-up of motor-operated actuators of basically ON/OFF control. 3200 series is featured by small-size. 3400 series use case, cover, mounting portion, etc. commonly with a full-electronic actuator. Explosion-proof approved models are also available.See here for models and details of specification.
Specifications
- Seeherefor Table of torque and thrust force.
- Seeherefor Explosion-proof approved models and specification.
| Principal uses | 2-position control | |
|---|---|---|
| Power | Drive motor | AC reversible motor |
| Power supply | Single phase 100V AC 50/60Hz | |
| Power supply - Optional |
Single phase 110/200/220V AC 50/60Hz | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact |
| Opening signal transmission - Optional |
Potentiometer (5kΩ/135Ω) | |
| Ancillary mechanism | Control position detection - Optional |
Auxiliary limit switch (voltfree), maximum points of detection 2 places |
| Overload protection | With built-in thermal protector | |
| Space heater - Optional |
* Please contact us for details, as this matter depends on the power supply voltage. | |
| Conditions for installation | Ambient temperature | -10 to 50° |
| Ambient temperature - With space heater |
-20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP54 or equivalent |
| Wiring port | G1/2 (2 place) | |
| Wiring port - Optional |
Various adaptors can be mounted | |
| Installation seat | Conforms to ISO | |
| Principal uses | 2-position control / Endless control / Multi-revolution control | |
|---|---|---|
| Power | Drive motor | AC reversible motor |
| Power supply | Single phase 100V AC 50/60Hz | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact |
| Input signal - With control pack |
4 to 20mA DC or 1 to 5V DC | |
| Opening signal transmission - Optional |
Potentiometer (5KΩ/135Ω) | |
| Ancillary mechanism | Control position detection-Optional |
Auxiliary limit switch (voltfree), maximum points of detection 2 places |
| Dismountable handle type, wit clutch- Optional |
Dismountable handle type, wit clutch | |
| Overload protection | With built-in thermal protector | |
| Space heater - Optional |
* Please contact us for details, as this matter depends on the power supply voltage. | |
| Control - Optional |
Control pack (endless type cannot be mounted) | |
| Conditions for installation | Ambient temperature | -10 to 50° |
| Ambient temperature - With space heater |
-20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP55 or equivalent |
| Wiring port | G1/2 (2 place) | |
| Wiring port - Optional |
Various adaptors can be mounted, Terminal box |
|
| Installation seat | Conforms to ISO | |
| Principal uses | 2-position control | |
|---|---|---|
| Power | Drive motor | AC reversible motor |
| Power supply | Single phase 100V AC 50/60Hz | |
| Power supply - Optional |
Single phase 110/200/220V AC 50/60Hz | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact |
| Opening signal transmission - Optional |
Potentiometer (5KΩ/135Ω) | |
| Ancillary mechanism | Control position detection - Optional |
Auxiliary limit switch (voltfree), maximum points of detection 2 places |
| Dismountable handle type | Dismountable handle type | |
| Overload protection | With built-in thermal protector | |
| Overload protection - Optional (3400R) |
Torque switch on closed side (CW direction only) | |
| Space heater - Optional |
* Please contact us for details, as this matter depends on the power supply voltage. | |
| Conditions for installation | Ambient temperature | -10 to 50° |
| Ambient temperature - With space heater |
-20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP55 or equivalent |
| Wiring port | G3/4 (3400R) G1/2 (3400L) 2 places | |
| Wiring port - Optional |
Various adaptors can be mounted Terminal box (3400L) |
|