Here is a line-up of motor-operated actuators of basically ON/OFF control. 3100 series is featured by small-size, lightweight and high output. 3400 series and 3420 series use case, cover, mounting portion, etc. commonly with a full-electronic actuator. 3900 series can be used for an inexpensive and simple instrumentation, with a potentiometer mounted for detection of control position, besides small size and lightweight. Explosion-proof approved models are also replete. See here for models and details of specification.
Specifications
- Seeherefor Table of torque and thrust force.
 - Seeherefor Explosion-proof approved models and specification.
 
| Principal uses | 2-position control | |
|---|---|---|
| Power | Drive motor | Synchronous motor | 
| Power supply | Single phase 100/110/200/220V AC 50/60 Hz | |
| Motor rating | 10 minutes | |
| Control mechanism | Input signal | Switching contact | 
| Ancillary mechanism | Overload protection | With built-in thermal protector | 
| Space heater - Optional  | 
                5W | |
| Conditions for installation | Ambient temperature | -10 to 50° | 
| Ambient temperature - With space heater  | 
                -20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP65 or equivalent | 
| Wiring port | G1/2 (1 place) | |
| Wiring port - Optional  | 
                Various adaptors can be mounted | |
| Installation seat | Conforms to ISO | |
| Principal uses | 2-position control | |
|---|---|---|
| Power | Drive motor | AC reversible motor | 
| Power supply | Single phase 100V AC 50/60Hz | |
| Power supply - Optional  | 
                Single phase 110/200/220V AC 50/60Hz | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact | 
| Opening signal transmission - Optional  | 
                Potentiometer (5kΩ/135Ω) | |
| Ancillary mechanism | Control position detection - Optional  | 
                Auxiliary limit switch (voltfree), maximum points of detection 2 places | 
| Overload protection | With built-in thermal protector | |
| Space heater - Optional  | 
                * Please contact us for details, as this matter depends on the power supply voltage. | |
| Conditions for installation | Ambient temperature | -10 to 50° | 
| Ambient temperature - With space heater  | 
                -20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP65 or equivalent | 
| Wiring port | G1/2 (1 place) | |
| Wiring port - Optional  | 
                Various adaptors can be mounted | |
| Installation seat | Conforms to ISO | |
| Principal uses | 2-position control / Endless control / Multi-revolution control | |
|---|---|---|
| Power | Drive motor | AC reversible motor | 
| Power supply | Single phase 100V AC 50/60Hz | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact | 
| Input signal - With control pack  | 
                4 to 20mA DC or 1 to 5V DC | |
| Opening signal transmission - Optional  | 
                Potentiometer (5KΩ/135Ω) | |
| Ancillary mechanism | Control position detection-Optional  | 
                Auxiliary limit switch (voltfree), maximum points of detection 2 places | 
| Dismountable handle type, wit clutch- Optional  | 
                Dismountable handle type, wit clutch | |
| Overload protection | With built-in thermal protector | |
| Space heater - Optional  | 
                * Please contact us for details, as this matter depends on the power supply voltage. | |
| Control - Optional  | 
                Control pack (endless type cannot be mounted) | |
| Conditions for installation | Ambient temperature | -10 to 50° | 
| Ambient temperature - With space heater  | 
                -20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP55 or equivalent | 
| Wiring port | G1/2 (1 place) | |
| Wiring port - Optional  | 
                Various adaptors can be mounted, Terminal box  | 
              |
| Installation seat | Conforms to ISO | |
| Principal uses | 2-position control | |
|---|---|---|
| Power | Drive motor | AC reversible motor | 
| Power supply | Single phase 100V AC 50/60Hz | |
| Power supply - Optional  | 
                Single phase 110/200/220V AC 50/60Hz | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact | 
| Opening signal transmission - Optional  | 
                Potentiometer (5KΩ/135Ω) | |
| Ancillary mechanism | Control position detection - Optional  | 
                Auxiliary limit switch (voltfree), maximum points of detection 2 places | 
| Dismountable handle type | Dismountable handle type | |
| Overload protection | With built-in thermal protector | |
| Overload protection - Optional (3400R)  | 
                Torque switch on closed side (CW direction only) | |
| Space heater - Optional  | 
                * Please contact us for details, as this matter depends on the power supply voltage. | |
| Conditions for installation | Ambient temperature | -10 to 50° | 
| Ambient temperature - With space heater  | 
                -20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP55 or equivalent | 
| Wiring port | G3/4 (3400R) G1/2 (3400L) 2 places | |
| Wiring port - Optional  | 
                Various adaptors can be mounted Terminal box (3400L)  | 
              |
| Installation seat | Conforms to ISO | |
| Principal uses | 2-position control | |
|---|---|---|
| Power | Drive motor | AC reversible motor | 
| Power supply | Single phase 100/110V AC 50/60Hz (+/- 5%) | |
| Power supply - Optional  | 
                Single phase 200/220V AC 50/60Hz (+/- 5%) | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact | 
| Opening signal transmission - Optional  | 
                Potentiometer (5KΩ/135Ω) | |
| Ancillary mechanism | Control position detection - Optional  | 
                Auxiliary limit switch (voltfree), maximum points of detection 2 places | 
| Dismountable handle type | With handle insertion hole | |
| Overload protection | With built-in thermal protector, Torque switch (3420R is an option)  | 
              |
| Space heater - Optional  | 
                * Please contact us for details, as this matter depends on the power supply voltage. | |
| Conditions for installation | Ambient temperature | -10 to 50° | 
| Ambient temperature - With space heater  | 
                -20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | Wiring port | G1/2 (2 places) | 
| Wiring port - Optional  | 
                Various adaptors can be mounted Terminal box  | 
              |
| Installation seat | Conforms to ISO | |
| Principal uses | 2-position control | |
|---|---|---|
| Power | Drive motor | AC reversible motor | 
| Power supply | Single phase 100/110V AC 50/60Hz (+/- 5%) | |
| Power supply - Optional  | 
                Single phase 200/220V AC 50/60Hz (+/- 5%) | |
| Motor rating | 30 minutes | |
| Control mechanism | Input signal | Switching contact | 
| Opening signal transmission - Optional  | 
                Potentiometer (1KΩ/135Ω) | |
| Ancillary mechanism | Control position detection - Optional  | 
                Auxiliary limit switch (voltfree), maximum points of detection 2 places | 
| Dismountable handle type | With handle insertion hole | |
| Overload protection | With built-in thermal protector | |
| Space heater - Optional  | 
                * Please contact us for details, as this matter depends on the power supply voltage. | |
| Conditions for installation | Ambient temperature | -10 to 50° | 
| Ambient temperature - With space heater  | 
                -20 to 40° | |
| Mounting position | Should not be mounted in an inverted position from the maintenance face. | |
| Body portion | External sheath type | Protection class IP65 or equivalent | 
| Wiring port | G1/2 (2 places) | |
| Wiring port - Optional  | 
                Various adaptors can be mounted, Terminal box  | 
              |
| Installation seat | Conforms to ISO | |