Motor-operated &Solid State Electronic Actuators
Explosion-proof of Specifications
Type | 3400R | 3500R | 3600R | |
---|---|---|---|---|
Type of explosion-proof structure | Pressuretight explosion-proof ExdBT4 |
Pressuretight explosion-proof ExdBT4 | Pressuretight explosion-proof ExdBT4 | |
Principal uses | 2-position control | Control | Control | |
Power | Drive motor | AC reversible motor | Brushless DC motor | AC reversible motor |
Power supply | Single phase 100V AC 50/60Hz |
Single phase 100V AC 50/60Hz |
Single phase 100V AC 50/60Hz |
|
Power supply Optional |
Single phase 110/200/220V AC 50/60Hz |
Single phase A110/200/220V AC 50/60Hz |
Single phase 110/200/220V AC 50/60Hz |
|
Motor rating | 30 minutes | Continuous | 30 minutes | |
Control mechanism |
Input signal | Switching contact | 4 to 20mA DC | 4 to 20mA DC or 1 to 5V DC |
Input signal Optional |
- | 1 to 5V DC/4 to 12mA DC/12 to 20mA DC | - | |
Opening signal transmission |
- | - | 4 to 20mA DC | |
Opening signal transmission Optional |
Potentiometer (5KΩ/135Ω) |
4 to 20mA DC with zero and span adjustment | - | |
Resolution | - | 0.3% (3/1000) | 0.8 to 1.0% (1/125 to 1/100) | |
Resolution Optional |
- | 0.2% (2/1000) | 0.4% (1/250) | |
Zero adjust range | - | +/-12.5% | +/-25% | |
Span adjust range | - | 5 to 100% | 20 to 100% | |
Operation | - | Either forward operation or reverse operation can be selected | Either forward operation or reverse operation can be selected | |
Ancillary mechanism |
Control position detection Optional |
Auxiliary limit switch (voltfree), maximum points of detection 2 places | - | Auxiliary limit switch (voltfree), maximum points of detection 2 places |
Manual operation mechanism |
Dismountable handle type | Dismountable handle type | Dismountable handle type | |
Sequence output signal |
- | Output shaft clockwise turned position | - | |
Sequence output signal Optional |
- | Output shaft counterclockwise turned position | - | |
Overload protection | With built-in thermal protector | With built-in overload protector | With built-in thermal protector | |
Overload protection Optional |
Torque switch on close side (CW direction only) | - | Overload unit, Torque switch on closed side (CW direction only) |
|
Space heater Optional |
* Please contact us for details, as this matter depends on the power supply voltage. | |||
Conditions for installation |
Ambient temperature | -10 to 50° | -10 to 50° | -10 to 50° |
Ambient temperature With space heater |
-20 to 40° | -20 to 40° | -20 to 40° | |
Mounting position | Should not be mounted in an inverted position from the maintenance face. | |||
Body portion | External sheath type | Protection class IP55 or equivalent | ||
Wiring port | G3/4 (2 places) | |||
Wiring port Optional |
Various adaptors can be mounted | |||
Installation seat | Conforms to ISO |
Type | 3400R | 3500R | 3600R | |
---|---|---|---|---|
Type of explosion-proof structure | Pressuretight explosion-proof ExdBT4 | Pressuretight explosion-proof ExdBT4 | Pressuretight explosion-proof ExdBT4 | |
Principal uses | 2-position control | Control | Control | |
Power | Drive motor | AC reversible motor | Brushless DC motor | AC reversible motor |
Power supply | Single phase 100V AC 50/60Hz |
Single phase 100V AC 50/60Hz |
Single phase 100V AC 50/60Hz |
|
Power supply Optional |
Single phase 110/200/220V AC 50/60Hz |
Single phase 110/200/220V AC 50/60Hz |
Single phase 110/200/220V AC 50/60Hz |
|
Motor rating | 30 minutes | Continuous | 30 minutes | |
Control mechanism |
Input signal | Switching contact | 4 to 20mA DC | 4 to 20mA DC or 1 to 5V DC |
Input signal Optional |
- | 1 to 5V DC/4 to 12mA DC/12 to 20mA DC | - | |
Opening signal transmission |
- | - | 4 to 20mA DC | |
Opening signal transmission Optional |
Potentiometer (5KΩ/135Ω) | 4 to 20mA DC with zero and span adjustment | - | |
Resolution | - | 0.3% (3/1000) | 0.8 to 1.0% (1/125 to 1/100) | |
Resolution Optional |
- | 0.2% (2/1000) | 0.4% (1/250) | |
Zero adjust range | - | +/-12.5% | +/-25% | |
Span adjust range | - | 5 to 100% | 20 to 100% | |
Operation | - | Either forward operation or reverse operation can be selected | Either forward operation or reverse operation can be selected | |
Ancillary mechanism |
Control position detection Optional |
Auxiliary limit switch (voltfree), maximum points of detection 2 places | - | - |
Manual operation mechanism |
Dismountable handle type | Dismountable handle type | Dismountable handle type | |
Sequence output signal |
- | Output shaft lowered position | - | |
Sequence output signal Optional |
- | Output shaft elevated position | - | |
Overload protection |
With built-in thermal protector | With built-in overload protector | With built-in thermal protector | |
Overload protection Optional |
- | - | Overload unit | |
Space heater Optional |
* Please contact us for details, as this matter depends on the power supply voltage. | |||
Conditions for installation |
Ambient temperature |
-10 to 50° | -10 to 50° | -10 to 50° |
Ambient temperature With space heater |
-20 to 40° | -20 to 40° | -20 to 40° | |
Mounting position | Should not be mounted in an inverted position from the maintenance face. | |||
Body portion | External sheath type |
rotection class IP55 or equivalent | ||
Wiring port | G3/4 (2 places) | |||
Wiring port Optional |
Various adaptors can be mounted | |||
Installation seat | Conforms to ISO |